Terminal block connection diagram – Fujimoto Fuji Differential Pressure Transmitter FKK 4 User Manual

Page 61

Advertising
background image

55

Tighten the terminal screws (M4 x10) to a torque of approximately 1.5 N•m (15 kgf•cm) <11ft-
lb> so that the wires will not loosen.
After connection, fasten the cover until it does not turn.

10.5 ~ 45 V DC (Analog type)
16.1 ~ 45 V DC (Smart type)

Output DC4 ~ 20mA

Terminal

CK+

CK–

+

Conveter

When using an external field indicator
For direct connection to an external field indicator, connect the “+” and “–” sides of the field
indicator to CK+ and CK– of the transmitter as shown below.
Use an external field indicator with internal resistance of 12W or less.

10.5 ~ 45 V DC (Analog type)
16.1 ~ 45 V DC (Smart type)

Output DC4 ~ 20mA

4 ~ 20mA DC


+

Converter

CK+

CK–

+

Terminal block connection diagram