2 power voltage and load resistance, Things convenient to know beforehand, Caution – Fujimoto Fuji Differential Pressure Transmitter FKK 4 User Manual

Page 62

Advertising
background image

56

Note) For communication with HHC, the smart type requires load resistance 250

as

minimum.

600

250

0

1533

Operating
zone

10.5

16.1

24

45

Power voltage (Vdc)

Load resistance (

)

Note

Hexagon key

wrench

Flash screw

When using conduit connection at the top
For wiring from the top conduit connection, use the following procedure.
(1)

Remove the screw plug of the top conduit connection.

(2)

Screw the removed screw plug into the bottom conduit connection.

(3)

Insert the cable from the top and connect it.

7.2 Power voltage and load resistance

Make sure the load resistance of the wiring connected to the loop is within the range shown below.

Things convenient to know beforehand

• The unused conduit connection is of great importance to flameproofing and

moisture prevention. So be sure to tighten the flush screw and packing into
the connection.

• When performing an insulation check after wiring, use a Megger (insulation

resistance meter) of 250 V DC or less and avoid applying a high voltage. If an
arrester is equipped, avoid the insulation resistance test and the dielectric
strength measurement.

Important

CAUTION

Connect power source of correct rating. Use of power source in excess of the
rating may cause a fire.