(1) Make wiring according to the diagram below.

Connect DC power supply (power source), digital voltmeter (measuring device), standard
resistance and HHC (Hand Held Communicator):
When current is measured with an ammeter connected to CK+ and CK- terminals, the internal
resistance of the ammeter should be 12

Ω or less.

(2) Calibration of output circuit (D/A)

Calibrate the output circuit with reference to “Calibration of output circuit” (page 20) in “AD-
JUSTMENT ”.

Load resistance

Standard resistance

DC power supply

Digital voltmeter

HHC

Important

For communication with the HHC, a load resistor of 250

Ω is necessary.

Calibration procedure

(3) Zero/span adjustment

Refer to “Zero/span adjustment” (page 35) in Section 7.

(4) Accuracy test

Apply input pressures in the order of 0%, 25%, 50%, 75%, 100%, 75%, 50%, 25% and 0%,
and read output at each input pressure.
Make sure the difference between each output value and input pressure (%) is within the
accuracy rating listed in the table below.
The voltage values in the table are dependent on use of “DC power supply + standard resistor
250

Ω + digital voltmeter (measuring device).

Measurement category

Reference value

Accuracy

Accuracy:0.1% Accuracy:0.2%

Percent display (%)

0, 25, 50, 75, 100

±0.1

±0.2

Current measurement (mA)

4, 8, 12, 16, 20

±0.016

±0.032

Voltage measurement (V)

1, 2, 3, 4, 5

±0.004

±0.008