Fig 1-2 : ups power switches configuration – Liebert 130 kVA User Manual

Page 22

Advertising
background image

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

2


During normal operation both the rectifier and inverter sections are active and provide

regulated load power whilst simultaneously float charging the battery. In the event of
a mains power failure, the rectifier becomes inoperative and the inverter is powered

solely from the battery. Critical load power is maintained under these conditions until

battery is fully discharged, where upon the UPS shuts down. The end of battery
discharge is assumed when the battery voltage falls below a preset value (i.e. 330 /

340V d.c. for a 400 V a.c. system).


The period for which the load can be maintained following a mains power failure is

known as the ‘System’s Autonomy Time’ and is dependent upon both the battery A/Hr

capacity and the applied percentage load.

1.2.2 Bypass Supplies

The circuit block annotated ‘Static Switch’ in figure 1-2 contains an electronically
controlled switching circuit which enables the critical load to be connected either to

the inverter output or to a bypass power source via the ‘static bypass line’. During

normal system operation the load is connected to the inverter and the ‘inverter -side’
of the Static Switch is closed; but in the event of a UPS overload, or inverter failure, it

is automatically transferred to the static bypass supply line.





















To provide a clean (no-break) load transfer between the inverter output and static
bypass line, the static switch activates connecting the load to the bypass supplies. To

achieve this, the inverter output and bypass supply must be fully synchronized during

normal operating conditions. This is achieved through the inverter control electronics
which make the inverter frequency track that of the static bypass supply provided that

the bypass remains within an acceptable frequency window. The synchronizing

window is pre-selected to 2% of nominal frequency, giving an acceptable frequency
window ±1 Hz.

A manually controlled, ‘Maintenance Bypass’ supply is also incorporated into the UPS
design. Its purpose is to enable the critical load to be powered from the mains

(bypass) supply while the UPS is shut down for routine maintenance.


Note: The load equipment is not protected from normal supply aberrations when operating on Bypass
side or in the maintenance bypass mode

Fig 1-2 : UPS Power switches configuration

RECTIFIER

STATIC

SWITCH

INVERTER

Bypass
Supply

Mains
Supply

UPS
Output
Supply

Battery
Isolator

Output

Isolator

Input

Isolator

Maintenance Bypass
Isolator

Maintenance Bypass Line

Static Bypass Line

Bypass Isolator

STATIC

SWITCH

BATTERY

Advertising