Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

19

3.2

Control cables


3.2.1

Battery Control

The battery circuit breaker is controlled by the Battery Circuit Breaker Controller Board

which is located within the Input Transformer Cubicle - or adjacent to the Battery

Circuit Breaker when the batteries are rack-mounted. This board controls the circuit
breaker’s undervolts release coil and also provides a path for the circuit breaker

auxiliary contacts to signal the circuit breaker status back to the UPS control logic. All

the connections between the controller board and the UPS module are made via the
Auxiliary Terminal Block which is located in the base of the UPS cabinet.




























Connect the battery circuit breaker control and temperature compensation cables

between the UPS auxiliary terminal block and battery circuit breaker controller board
as shown in figure 3-3. These cable must be shielded, shield should be connected at

protective earth of Input transformer cubicle or battery breaker, not of UPS.

CAUTION

If battery temperature compensation is not used the system must be
de-activated by commissioning engineer.

Fig 3-2 : Auxiliary Terminal Block detail

1

2

3

4

5

B A T T E R Y C I R C U I T

B R E A K E R C O N T R O L L E R

B O A R D

X1

1

2
3
4

5
6
7

8
9

10
11
12

X3

1
2
3

4
5
6

7
8
9

10
11
12

X4

LINKS

Ext OFF Inv.

Ext Sw. Out

Ext EPO

Ext BYP

Back feed

Int EPO

Common
I batt.
Common
Batt. Sw.
Batt. trip

AUXILIARY

TERMINAL

BLOCK

LOCATED IN

UPS

CABINET