Specification, 1 conformity and standard, 2 ups environmental – Liebert 130 kVA User Manual

Page 91: 3 ups mechanical characteristics

Advertising
background image

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

71

Chapter 9

Specification

This specification describe requirements for an Uninterruptible Power System (UPS).

9.1

Conformity and Standard

The UPS has been designed to conform the following standards: IEC, EN

9.2

UPS Environmental

The UPS shall be able to operate under the following environmental conditions without

damage or degradation in electrical operating characteristics:

Environmental Characteristics

Units

Rated Power

kVA

130

Operating Temperature

ºC

0 to 45 ºC

Relative Humidity

%

= 90% at 31 ºC, Saliferrous, Humid

Altitude of operation

m

= 1000m above sea level

Storage/ transport temperature

ºC

-25 to 70 ºC

9.3

UPS Mechanical Characteristics

Mechanical
Characteristics

Units

130 kVA

6 pulse

Height

mm

1900

Width

mm

1400

Depth

mm

925

Ventilation

-

By internal intake fans

Cable entry

-

Bottom

Protection

IP

41