Liebert 130 kVA User Manual

Page 59

Advertising
background image

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

39



WARNING

Wait 5 minutes for the internal D.C. busbar capacitors
to discharge.

The UPS is now completely powered down.

IMPORTANT

The Maintenance Bypass Power switch may be
operated at any time when the UPS is powered down
to connect the load to the maintenance bypass supply
if required.

The load equipment is not protected from normal
supply aberrations when operating in the
maintenance bypass mode.


5.7

Procedure for carrying out a RESET after a recognized

controlled transfer to bypass or EPO action.

When the necessary action to correct the problem has been taken, this procedure
should be followed to restore the UPS back to its normal operating condition following,

a controlled transfer to bypass or when the Remote Emergency Power Off has been

activated.

A recognized controlled transfer to bypass is activated by the following problems:

Inverter Overtemperature, Cut-off Overload, Battery Over voltage, when configured for
manual return from bypass operation (only for system test).


Press the ENTER key.


Note: In ECOMODE the message 'LOAD ON BYPASS'
will not appear.

Select FUNCTION and press ENTER key.





When the PASSWORD has been completed press
ENTER key.



EMERGENCY STOP

LOAD ON BYPASS

INV: UNSYNCHRONISED

hh.mm.ss dd.mm.yy

EMERGENCY STOP

LOAD ON BYPASS

INV: UNSYNCHRONISED

hh.mm.ss dd.mm.yy

MEASUREMENT

>FUNCTION <

MAINTENANCE

SETUP

MEASUREMENT

>FUNCTION <

MAINTENANCE

SETUP

WRITE SAVE

MOVE EXIT ESC

ENTER PASSWORD

00000000

WRITE SAVE

MOVE EXIT ESC

ENTER PASSWORD

00000000