Liebert 130 kVA User Manual

Page 95

Advertising
background image

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

75


9.7 UPS Electrical Characteristics (Bypass Input Mains)

B Y P A S S I N P U T M A I N S

Rated Power

kVA

130

Rated mains voltage j

Vac

380 - 400 - 415

Supply

Three phase with neutral

Rated Current:
110 Vac

A

1182

Bypass voltage tolerance k

%

± 10

Delay time to recognize bypass
voltage returned to window

sec

10

Inverter output voltage window

%

± 10

Frequency l

Hz

50 or 60

Input frequency tolerance m

%


± 2

Maximum frequency slew rate

Hz

/sec

0.1

Current rating of neutral cable

1.5 x In

Protection, bypass line

To avoid series fuses, the bypass line should be protected using an

external device should be sized to discriminate with the load

protection.

Overload

%

150% for 60 sec

125% for 10 min

110% for 1 hr


Note:
j

= Factory set 400V – 380V or 415V set changing taps on auxiliary supply transformer and with software setting

k

= Other values 0-15% with software setting.

l

= Factory set at 50Hz ; 60Hz with software setting.

m

= Other values 1-9% with software setting.