Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

74


9.6

UPS Electrical Characteristics (Inverter Output)

I N V E R T E R O U T P U T

Rated Power

kVA

130

Rated mains voltage j

Vac

380 - 400 - 415

Three phase with neutral

Frequency k

Hz

50 to 60

Rated Power at cos

φ

= 0.8

KVA

130

Rated Power at cos

φ

= 1

KW

104

Overload

%

150% FOR 60 sec

125% for 10 min

110% for 1 hr

Maximum non linear load

allowed l

-

100% Pn

Voltage stability, steady state test

m

%


± 1.5

Voltage stability, transient test n

%

± 5

Maximum rate of change of
frequency o

Hz

/sec

0.1


Note:
j

= Factory set 400V – 380V or 415V voltages with software setting

k

= Factory set at 50Hz ; 60Hz with software setting.

l

= EN50091-3 (1.4.58) crest factor 3.

m

= EN50091-3 (4.3.4).

n

= EN50091-3 (4.3.7) also for 0-100% load transient, restore time 20ms to ±1%.

o

= Factory set at 0.1Hz/ sec; upto 2 Hz/sec with software setting.