Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

73


9.5

UPS Electrical Characteristics (DC Intermediate Circuit)

D. C. I N T E R M E D I A T E C I R C U I T

Rated Power

kVA

130

Voltage range for Inverter operation

Vdc

340 – 480

Recommended number of

-

Lead-acid cells j-k


-

Ni-Cd cells j-k

Nos.

190 (380 Vac)
198 (400 Vac)
204 (415 Vac)

320 (454.4 Vac)

Recommended float charge voltage
2.25 V/cell (Lead Acid) j


1.42 V/cell (Ni-Cd) j

Vdc

432 (380 Vac)
446 (400 Vac)
459 (415 Vac)

454.4 Vac

Recommended boost charge voltage
2.40 V/cell (Lead Acid) j


1.55 V/cell (Ni-Cd) j

Vdc

460 (380 Vac)
475 (400 Vac)
490 (415 Vac)

480 Vac

Recommended end of discharge voltage

1.67 V/cell (Lead Acid) j


1.1 V/cell (Ni-Cd) j

Vdc

320 (380 Vac)

330 (400 Vac)
340 (415 Vac)

340 Vac

Recommended test voltage
for Lead Acid j


for Ni-Cd j

Vdc

365 (380 Vac)
376 (400 Vac)
388 (415 Vac)

384 Vac

Battery boost charge cycle l

-


Characteristics to DIN 41772I-U, boost to floating charge

switching, with current measuring criterion plus control of

charging time.

Maximum boost charge duration l

min

0-999

Boost-float threshold current l

A

0-99

Ripple voltage superimposed m

%

2


Note:
j

= (According to rated voltage)

k

= Factory set for rated 400V, different cells number and voltage per cell may be set by software and / or

trimmers on Rectifier control board.

l

= Set by software

m

= Battery disconnected, RMS percentage value referred to DC voltage.