Liebert 130 kVA User Manual

Page 40

Advertising
background image

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

20


3.2.2

Auxiliary Terminal Block X3 and X4 at UPS

X3 terminal reference

Reference label

Description

2

Common

Temperature sensor common (0V)

3

T Batt.

Temperature sensor signal

4

Common

Common (0V)

5

Batt. Sw.

Battery circuit breaker trip control

6

Bat Trp

Battery circuit breaker trip control


Note:
The auxiliary cables of the battery must be screened and double insulated.

The screen is connected to the earth of the battery cabinet or supporting rack.
Use multiple-core shielded cables with a section of 0.5 to 1mm

2

Connect the cables with the Fast-on 6.3 x 0.8 mm terminals (female)

X4 terminal reference

Reference label

Description

1-2

Ext. OFF Inv

Remotely provides control for switching off the inverter.
Normally open contact.

3-4

Ext. Sw. Out

Indication to be provided at the UPS to note the opening of an external
module output isolator.
Normally closed contact.
If unused, leave the standard connectors in place.

5-6

Ext. EPO

Remotely provides control for switching off the UPS using a remote
emergency button.
Normally closed contact.
If unused, leave the standard connectors in place.

7-8

Ext. BYP

Indication to be provided at the UPS to note the opening of an external
maintenance bypass switch.
Normally closed contact.

If unused, leave the standard connectors in place.

9-10

Back Feed

Signal form the UPS to indicate a return flow of energy in the bypass mais.
Normally open contact.

11-12

Int. EPO

Availability of a contact for switching off the UPS in the same way as the
internal emergency off button.

Normally closed contact.


Note:
All auxiliary cables of terminal block X4 must be double insulated.

The cross-sectional area of the auxiliary cables is from 0.5 to 1 mm

2

Connect the cables with the Fast-on 6.3 x 0.8 mm terminals (female)
Maximum contact rating on auxiliary terminals: 50 Vdc @ 1 Amp.