Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

14


3.1.2

Cable rating

NOMINAL CURRENT (Amps)

3 Phase Input Mains with full

battery re-charge

(less 5% for 12 pulse)

1 Phase Output at full load

Battery at minimum

Battery Voltage

UPS

Rating

(kVA)

380V

400V

415V

110V

115V

120V

380V

400V

415V

30

63

60

58

272

260

250

83

80

77.5

40

84

80

77

364

349

334

110

106

103

50

105

100

96

454

434

416

137

133

129

60

126

119

115

545

521

500

164

159

155

80

165

157

151

727

695

666

219

213

206

120

245

233

223

1090

1043

1000

329

319

310

130

259

247

238

1181

1130

1083

357

346

336

150

300

285

275

1363

1304

1250

412

399

387

Table 3-1 UPS Module cabinet power cable rating



3.1.3

General Notes

The following are guidelines only and superseded by local regulations and codes of
practice where applicable:

1. The neutral conductor should be sized same as the output/ bypass current.

2. The earth conductor should be sized for carrying fault current for atleast 3 to 5

seconds or as guided by local electrical rules.

3. Consideration should be given to the use of paralleled smaller cables for heavy

currents, as this can ease installation considerably.

4. When sizing battery cables, a maximum volt drop of 3V d.c. is permissible at the

current ratings given in Table 3-1.

3.1.4

Cable Connections

The rectifier input, bypass, output and battery power cables (all require lug type

terminations) and are connected to busbars situated below the power isolator
switches - as shown in figure 3.1 for 80kVA and fig 3.2 for 120 /160/ 200kVA.

A terminal block X3 is used for connecting the control cables to the battery circuit
breaker and a second terminal block X4 is used for the external emergency stop

facility, external OFF inverter, ext. Bypass, etc. these are female spade type

connections (Fast-on 6.3 x 0.8) and are described later in Section 3.2


3.1.5

Safety earth

The safety earth busbar is located between the Bypass and Output power supply
connections as shown in the figure 3.1. The safety earth cable must be connected to

the earth busbar and bonded to each cabinet in the system.


All cabinets and cable trunking should be earthed in accordance with local

regulations.