Liebert 130 kVA User Manual

Page 55

Advertising
background image

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

35





Select MEASUREMENT and press ENTER key.



Select BATTERY and d.c. busbar voltage will be
displayed:


If the voltage indicated is satisfactory (432V d.c. for
380V a.c. system, 446VV d.c. for 400V a.c. system
and 459V d.c. for a 415V a.c. system) press the
Escape key repeatedly until the display returns to
the original window.

6. Manually close the battery circuit breaker. This
is located inside the battery cabinet (if used) or is

otherwise located adjacent to the battery racks.

The Module Mimic indicator (3) Battery unavailable
should extinguish. Several LED’s on the Battery
state of charge bargraph (17) will illuminate
showing the battery state of charge

When the battery circuit breaker has been closed
and the inverter has stabilized the screen will

change to the default window.


Default window:

The message shown below, will be seen on the
default screen whenever the UPS is operating
normally:

The top lines display the UPS operational status
and indicates alarm conditions when they occur;
and line four normally shows the time and date.


The UPS is operating normally with its

Inverter supplying the load.


ECOMODE:
The following message will appear in the default

screen whenever the UPS is operating in
ECOMODE. The load is supplied through Bypass
Mains.


The UPS is operating in ECOMODE with the Bypass

Mains supplying the load.

>MEASUREMENT <

FUNCTION
MAINTENANCE
SETUP

>MEASUREMENT <

FUNCTION
MAINTENANCE
SETUP

OUTPUT
INPUT

>BATTERY <

TEMPERATURE

OUTPUT
INPUT

>BATTERY <

TEMPERATURE

BATTERY
VOLTAGE 446 [V]
CURRENT 001 [A]
CHARGE 000 [%]

BATTERY
VOLTAGE 446 [V]
CURRENT 001 [A]
CHARGE 000 [%]

NORMAL OPERATION

hh.mm.ss dd.mm.yy

NORMAL OPERATION

hh.mm.ss dd.mm.yy

NORMAL OPERATION
(ECOMODE)

hh.mm.ss dd.mm.yy

NORMAL OPERATION
(ECOMODE)

hh.mm.ss dd.mm.yy