Liebert 130 kVA User Manual

Page 53

Advertising
background image

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

33


The Display window will show the present status

of the UPS

3. Close the Rectifier input power switch Q1.


Note:

In ECOMODE the message 'LOAD ON BYPASS' will not
appear.


4. Wait for 20 seconds then close the battery circuit

breaker. This is located inside the battery cabinet
(if used) or is otherwise located adjacent to the
battery racks.

The Module Mimic indicator (3) Battery unavailable
should extinguish. Several LED’s on the Battery
state of charge bargraph will illuminate showing the
battery state of charge.


The rectifier will ‘walk-in’ and stabilize at float the
voltage.

5. Open the Maintenance Bypass power switch Q3
and fit lock.

The Module mimic indicator Load on bypass (6)
will flash amber.


The Display window will show the present status of
the UPS.


6. After 5 seconds the Module Mimic LED’s will
change so that the Load on inverter (5) will light
steady green and the Load on Bypass (6) will
extinguish.

Note: In ECOMODE the Load on Mains led (6) stays on
while the Load on inverter led (5) is off.


The message shown below, will be seen on the
Default screen whenever the UPS is operating
normally.

The UPS is operating normally with its

Inverter supplying the load

ECOMODE: The following message will appear in
the default screen whenever the UPS is operating
on ECOMODE. The load is supplied by the Bypass
Mains.


The UPS is operating in ECOMODE with the Bypass

Mains supplying the load.

RECTIF. SWITCH OPEN
BATTERY C.B. OPEN
MANUAL BYPASS CLOSED
hh.mm.ss dd.mm.yy

RECTIF. SWITCH OPEN
BATTERY C.B. OPEN
MANUAL BYPASS CLOSED
hh.mm.ss dd.mm.yy

LOAD ON BYPASS
MANUAL BYPASS CLOSED
INV. OFF
hh.mm.ss dd.mm.yy

LOAD ON BYPASS
MANUAL BYPASS CLOSED
INV. OFF
hh.mm.ss dd.mm.yy

LOAD ON BYPASS
INV.: OFF

hh.mm.ss dd.mm.yy

LOAD ON BYPASS
INV.: OFF

hh.mm.ss dd.mm.yy

NORMAL OPERATION

hh.mm.ss dd.mm.yy

NORMAL OPERATION

hh.mm.ss dd.mm.yy

NORMAL OPERATION
(ECOMODE)

hh.mm.ss dd.mm.yy

NORMAL OPERATION
(ECOMODE)

hh.mm.ss dd.mm.yy

Advertising