Fig 4-2: single module operator control panel – Liebert 130 kVA User Manual

Page 44

Advertising
background image

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

24



4.1.1

Operator control panel

The control and display panel LEd indications are illustrated in figure 4-2 and
described in the following text:




















Mimic indications

Six LED’s mounted on a single line diagram represents the various UPS power paths

and show the current UPS operation status:


1. Bypass supply healthy

This led illuminates when the bypass a.c. input power switch is closed and the input

supply is within of set value nominal voltage (default ±10%)


2. Input supply healthy and Rectifier is operative.

3. Battery voltage healthy (i.e. between ‘under - voltage cut-off’ and ‘over - voltage
trip’ levels).

4. Inverter output healthy.

5. Load on Inverter status

This led illuminates when the output power switch is closed and the load is connected
to the inverter.

6. Load on Bypass status.
This led illuminates when the output power switch is closed and the load is connected

to the bypass a.c. supply via the static switch.



Inverter control switch

7. Inverter ON (Only for UPS above 80kVA rating) - Manual inverter selection switch.

8. Inverter LED - inverter status indicator contained within the switch icon.

The Inverter LED (yellow) indicates when the Inverter is switched OFF.

Fig 4-2: Single module operator control panel