Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

13



CHAPTER 3

Installation (Electrical)


The UPS requires both “Power” and “Control” cabling once it has been mechanically
installed. All Control cables, whether screened or not, should be run separate from

the Power cables in metal conduits or metal ducts which are electrically bonded to the

metalwork of the cabinets to which they are connected.

3.1

Power Cabling

WARNING

Before cabling-up the UPS, ensure that you are aware of the location
and operation of the external isolators that connect the UPS input/
bypass supply to the mains distribution panel.

Check that these supplies are electrically isolated, and post any
necessary warning signs to prevent their inadvertent operation.


For cable entry, refer to section 2.3.5

3.1.1

System Configuration

The power cables of the system must be size with respect to the following description:

Module input cables

The module input cables must be sized for the maximum input current, including the

maximum battery recharge current, given in the table 3-1, with respect to the module

rating and the input a.c. voltage.


Module Bypass and Output cables

The Bypass and Output cables must be sized for the nominal output current, given in
the table 3.1, with respect to the module rating and the output a.c. voltage.


Battery cables

Each UPS module has its own battery, which is connected using two cables, one

positive and one negative. The battery cables must be sized for the battery discharge

current at the end-of-discharge voltage, as given in the table 3-1, with respect to the
module rating.