Liebert 130 kVA User Manual

Page 89

Advertising
background image

User Manual

Hipulse - Single Phase ‘1+N’ UPS System

130 kVA - 110V

69


8.3.1.2 Switching the system to maintenance bypass from normal operation


WARNING

The internal maintenance bypass must not be used when the UPS
system is comprised of more than two UPS modules in parallel.


Follow the procedure for the single UPS by referring to Chapter 5 – Operating

Instructions: Paragraph 5.4. For a system configured in the “1+N system”, the

changeover from “load on inverter ” to “load on bypass” will occur only when the
operation described in point 3 has been completed on both UPS modules.

8.3.1.3 Switching the system ON from a maintenance power down condition.

Follow the procedure for single UPS, referring to Chapter 5 – Operating Instructions:

Paragraph 5.2 .

8.3.1.4 Switching OFF and isolating one UPS while the other remains in service.

1. In sequence, open the UPS isolators Q4 (output), Q1 (rectifier input), Q2 (bypass

input).

2. Open the circuit-breaker inside the battery cabinet.


To completely isolate the UPS, open the a.c. power supply circuit-breaker (both circuit

breakers if separate supplies are provided for the rectifier and the bypass supply) and

thee output circuit breaker on the power distribution switchboard.

If individual UPS output isolation circuit-breaker (and its auxiliary contacts) are not

installed on the power distribution switchboard, remember that voltage supplied by
the others UPS which remains in service still will be present on the output terminals of

the shutdown UPS.



WARNING

If individual UPS output isolation circuit-breaker are not installed on
the power distribution switchboard, remember that voltage supplied
by the others UPS remains in service will still be present on the output
terminals of the shutdown UPS.

Warning : Wait 5 minutes for the internal d.c. busbar
capacitors to discharge.