RIO Remote I/O System User Guide
Installing a Long Distance Module (LDM)

Page 179

Chapter 2 Installing hardware and software

Installation

General procedure

To install a long distance module proceed as follows;

1. On the LDU, set the speed and protocol you want by setting the rotary switch on each

LDU (shown on

page 178

) using a small screwdriver. The settings available are shown in

the next table.

2. Install the type of LDU link you want. For Modem via telephone line see

page 180

, for

long wire see

page 180

and for X.21 see

page 180

.

Note

For modem installations, you need to use a converter cable to connect the LDU DB25 flying lead to the
modem. On long-wire installations, the long-wire you can connect directly to the DB25 flying lead.

For information on how to wire up the converters needed for each type of installation see

Adaptor pinouts

for LDU flying lead connectors

on page

186

.

Device

Line Speed

Transmission type

Use switch
setting

Modem

9600

Asynchronous

0

Modem

19200

Asynchronous

1

Modem

38400

Asynchronous

2

Reserved address, do not use

3

Reserved address, do not use

4

Long wire

78000

Asynchronous

5

Long wire

156250

Asynchronous

6

Long wire

312500

Asynchronous

7

Modem

Synchronous

8

X21 bis

Synchronous

9

X21

Synchronous

A

Reserved address, do not use

B

Modem with Autodial

9600

Asynchronous

C

Modem with Autodial

19200

Asynchronous

D

Modem with Autodial

38400

Asynchronous

E

Reserved address, do not use

F