Toshiba Tosvert VF-AS1 User Manual
Page 106

E6581301
E-40
5
■
Minimum resistance of connectable braking resistors
The minimum allowable resistance values of the externally connectable braking resistors are listed in the table
below.
Do not connect braking resistors with smaller resultant resistance than the listed minimum allowable resistance
values.
(For 200kW or greater models, a dynamic braking resistor drive unit (optional separate unit) is needed.)
200V Class
400V Class
Inverter
Related output capacity
(kW)
Resistance of
standard option
Minimum allowable
resistance
Resistance of
standard option
Minimum allowable
resistance
0.4
200Ω
50Ω
–
–
0.75
200Ω
50Ω
200Ω
60Ω
1.5
75Ω
35Ω
200Ω
60Ω
2.2
75Ω
25Ω
200Ω
60Ω
3.7/4.0
40Ω
16Ω
160Ω
40Ω
5.5
20Ω
11Ω
80Ω
30Ω
7.5
15Ω
8Ω
60Ω
30Ω
11
10Ω
5Ω
40Ω
20Ω
15
7.5Ω
5Ω
30Ω
20Ω
18.5
7.5Ω
5Ω
30Ω
15Ω
22
3.3Ω
3.3Ω
15Ω
13.3Ω
30
3.3Ω
2.5Ω
13.3Ω
10Ω
37
2Ω
1.7Ω
8Ω
6.7Ω
45
2Ω
1.7Ω
8Ω
5Ω
55
2Ω
1.7Ω
8Ω
5Ω
75
1.7Ω
1.3Ω
8Ω
3.3Ω
90
–
–
3.7Ω
2.5Ω
110
–
–
3.7Ω
1.9Ω
132
–
–
3.7Ω
2.5Ω
160
–
–
3.7Ω
1.3Ω
200
–
–
1.9Ω
1Ω
220
–
–
1.9Ω
1Ω
280
–
–
1.4Ω
1Ω
355
–
–
400
–
–
500
–
–