Toshiba Tosvert VF-AS1 User Manual

Page 201

Advertising
background image

E6581301

G-7

7

Parameter setting

Positive

logic

Negative

logic

Function

Operation output specifications (in case of positive logic)





Over-torque detection

ON:The state that torque component is H, H set
value or larger continued more than H set value.





Braking resistor
overload pre-alarm

ON:A certain rate of braking resister overload trip (QNT)
detection time is over.
OFF:The detection time is within a certain limit.





In emergency stop

ON:In emergency stop operation (G is indicated).
OFF:The detection time is within a certain limit.





In retry

ON:In retry operation (TVT[ is indicated).
OFF:No retry operation is performed.





Pattern operation
switching output

ON:In normal operation or pattern operation has finished.
OFF:In pattern operation.





PID deviation limit

ON:PID deviation is in H or H set value.





Run/Stop

ON:Running frequency is output or DC injection breaking (FD) is
performed.





Serious failure (OCA,
OCL, EF, phase failure,
etc.)

ON:Serious failure (QEC, QEN, GH, phase failure, abnormal
output, short-circuit) is detected.
OFF:Inverter has recovered from serious failure. (Serious failure
has been reset)





Light failure (OL, OC1,
2, 3, OP)

ON:Light failure (QN, QE, QE, QE, QR) is detected.
OFF:Inverter has recovered from light failure. (Light failure has
been reset)





Commercial
power/inverter
switching output 1

Refer to Section 6.19.





Commercial
power/inverter
switching output 2

Refer to Section 6.19.





Cooling fan ON/OFF

ON:Cooling fan is in operation.
OFF:Cooling fan is off operation.





In jogging operation
(In jog run)

ON:In jog run
OFF:In normal operation





Operation
panel/terminal board
operation switching

ON:In operation by terminal board.
OFF:In operation by operation panel.





Cumulative operation
time alarm

ON:Cumulative operation time is beyond the H set value.
OFF:Cumulative operation time is less than the H set
value.





PROFIBUS/DeviceNet/CC
-Link communication error

ON:Communication error occurred.
OFF:Communication error is canceled (reset).





Forward/reverse
switching

OFF:In forward operation.
ON:In reverse operation.
(The last status is held while operation is suspended.)





Ready for operation 1

ON:In operable status or operation can be started with frequency
command input as an operation switching answer-back.
OFF:In inoperable status.





Ready for operation 2

ON:In operable status or operation can be started with ST and
RUN signals and frequency command input.
OFF:In inoperable status.





Brake release (BR)

Output the braking signal according to the brake sequence.





In (pre-)alarm status

ON:More than one of alarm, pre-alarm, undervoltage, low current
over-torque, poor control power supply, PID deviation limit,
abnormal frequency setting or torque limit have occurred or
detected.
OFF:All the alarms above are canceled.





Forward speed limit
(torque control)

ON:Forward operation speed is H set value or over.
OFF:Forward operation speed is less than H set value.





Reverse speed limit
(torque control)

ON:Reverse operation speed is Hset value or over.
OFF:Reverse operation speed is less than H set value.





Inverter healthy output

ON and OFF are alternately output at intervals of 1 second.





RS485
communication error

ON:Communication error occurred.
OFF:Communication error is canceled (reset).





Error code output 1





Error code output 2





Error code output 3





Error code output 4





Error code output 5





Error code output 6

Output the error code in 6-bit.