Jog run mode

H

: Jog run frequency

H

: Jog run stop pattern

H

: Operation panel jog run mode

• Function

Use the jog run parameters to operate the motor in jog mode. Input of a jog run signal generates a jog run
frequency output at once, irrespective of the designated acceleration time.
Also, you can choose an operation panel start/stop mode between the ordinary start/stop mode and the jog
run start/stop mode.

The jog run function needs to be assigned to an input terminal.
When assigning it to the S3 terminal, set H to .
The motor can be operated in jog run mode while the jog run setting terminals are connected (S3-CC: ON).

[Parameter setting]

Title

Function

Adjustment range

Default setting

H

Jog run frequency

H

~Hz



H

Jog run stop pattern



:Deceleration stop, : Coast stop,



:DC braking stop



H

Operation panel jog run mode



:OFF,



:Operation panel jog run mode enabled



<Examples of jog run>

S3-CC (JOG) ON + F-CC ON: Forward jog run

S3-CC (JOG) ON + R-CC ON: Reverse jog run

( Normal operation frequency signal input + F-CC ON: Forward run, Normal operation frequency signal input + R-CC ON: Reverse run )

ST-CC

F-CC

R-CC

S3-CC

Input of operation
frequency setting signal

Output frequency [Hz]

Forward
run

Reverse
run

Forward
run

Forward run

0

Set frequency

Time [s]

• The jog run setting terminal (S3-CC) is enabled when the operation frequency is below the jog run frequency.

This connection does not function at an operation frequency exceeding the jog run frequency.

• The motor can be operated in jog mode while the jog run setting terminals are connected (S3-CC: ON).
• Jog run has priority, even when a new operation command is given during operation.
• Even during panel operation (EOQF =), the inverter can be switched forcibly to jog run mode by turning on or

off the input terminal if parameter H (input terminal priority selection) is set to  and the jog run setting
function (, ) is assigned to the input terminal.

• Even for H= or , an emergency DC braking becomes enabled when setting H=.
• If a forward run command and a reverse run command are entered simultaneously while H (priority selection

(both F-CC and R-CC are ON)) is set to  (reverse run), operation modes are switched as follows: forward jog run
→ deceleration stop (jog frequency → 0Hz) → reverse jog run. Keep this in mind.

• The jog frequency is not restricted by the upper limit frequency (WN).