35 adjustment parameters – Toshiba Tosvert VF-AS1 User Manual

Page 177

Advertising
background image

E6581301

F-65

6

6.35

Adjustment parameters

6.35.1 Pulse train output for meters

H

: Logic output/pulse output selection (OUT1)

H

: Pulse output function selection

H

: Selection of number of pulses

H

: Constant at the time of filtering

H

: FM output filter

Function

Pulse trains can be sent out through the OUT1-NO output terminals.
To do so, it is necessary to select a pulse output mode and specify the number of pulses.

Set the SW4 to pulse output (PULS).
Ex.) When operations frequencies (0 to 60Hz) are put out by means of 0 to 10kHz

HJ

=, H=, H=, H=

The pulse will change between 0 and 10kHz according to the operations frequencies between 0 and 60Hz.

Title

Function

Adjustment range

Default setting

H

Logic output/pulse output selection
(OUT1)



:Logic output



:Pulse output



H

Pulse output function selection



:Output frequency



:Frequency command value



:Output current



:Input voltage (DC detection)



:Output voltage



:Compensated frequency



:Speed feedback

(realtime value)



:Speed feedback (1-second filter)



:Torque



:Torque command



:Torque current



:Exiting current



:PID feedback value



:Motor overload factor (OL2 data)



:Inverter overload factor (OL1 data)



:Regenerative braking resistance

overload factor (OLr data)



:Regenerative braking resistor load

factor (% ED)



:Input power



:Output power



:Optional AI2 input



:RR/S4 input



:VI/II input



:RX input



:Optional AI1 input



:FM output



:AM output



:Fixed output 1



:Communication data output



:Fixed output 2



:Fixed output 3



:Cumulative input power



:Cumulative output power



:My function monitor 1



:My function monitor 2



:My function monitor 3



:My function monitor 4



H

Selection of number of pulses



.~.kHz



H

Constant at the time of filtering



msec, msec~msec



H

FM output filter



:No filter



:Filter approx. 10ms



:Filter approx. 15ms



:Filter approx. 30ms



:Filter approx. 60ms



Note: The pulse length is fixed. Therefore, the duty is variable.

Advertising