Toshiba Tosvert VF-AS1 User Manual

Page 257

Advertising
background image

K-19

E6581301

11

[21] Adjustment parameters [2/2]

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control V/f Constant Reference

H

0478

Optional AI2 input bias

0~255

1/1

*1

Enabled

●/●

●/●

6. 28

H

0479

Optional AI2 input gain

0~255

1/1

*1

Enabled

●/●

●/●

6. 28

H

0498

PM motor constant 1 (d axis

inductance)

0~100%

1/1

40

Disabled

-

-

-

6. 29

H

0499

PM motor constant 2 (q axis

inductance)

0~100%

1/1

40

Disabled

-

-

-

6. 29

*1:

Settings vary from unit to unit. Even if V[R is set to , no change is made to these values.

[22] Acceleration/deceleration 2 [1/2]

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control V/f Constant Reference

H

0500

Acceleration time 2

0.1~6000 sec.

0.1/0.1 *2

*1

Enabled

●/●

-

6. 30. 1

H

0501

Deceleration time 2

0.1~6000 sec.

0.1/0.1 *2

*1

Enabled

●/●

-

6. 30. 1

H

0502

Acceleration/deceleration 1

pattern

0:Straight, 1:S-pattern 1, 2:S-pattern 2

1/1

0

Enabled

●/●

-

6. 30. 1

H

0503

Acceleration/deceleration 2

pattern

0:Straight, 1:S-pattern 1, 2:S-pattern 2

1/1

0

Enabled

●/●

-

6. 30. 1

H

0504

Acceleration/deceleration 1, 2,

3, 4 selection

1:Acceleration/deceleration 1

2:Acceleration/deceleration 2

3:Acceleration/deceleration 3

4:Acceleration/deceleration 4

1/1

Enabled

●/●

-

6. 30. 1

H

0505

Acceleration/deceleration

switching frequency 1

0.0~HJ Hz

0. 1/0.01

0.0

Enabled

●/●

-

6. 30. 1

H

0506

Acceleration S-pattern lower

limit adjustment

0~50%

1/1

10

Enabled

●/●

-

6. 30. 1

H

0507

Acceleration S-pattern upper

limit adjustment

0~50%

1/1

10

Enabled

●/●

-

6. 30. 1

H

0508

Deceleration S-pattern lower

limit adjustment

0~50%

1/1

10

Enabled

●/●

-

6. 30. 1

H

0509

Deceleration S-pattern upper

limit adjustment

0~50%

1/1

10

Enabled

●/●

-

6. 30. 1

H

0510

Acceleration time 3

0.1~6000 sec.

0.1/0.1 *2

*1

Enabled

●/●

-

6. 30. 1

H

0511

Deceleration time 3

0.1~6000 sec.

0.1/0.1 *2

*1

Enabled

●/●

-

6. 30. 1

H

0512

Acceleration/ deceleration 3

pattern

0:Straight, 1:S-pattern 1, 2:S-pattern 2

1/1

0

Enabled

●/●

-

6. 30. 1

H

0513

Acceleration/deceleration

switching frequency 2

0.0~HJ Hz

0.1/0.01

0.0

Enabled

●/●

-

6. 30. 1

*1: Default values vary depending on the capacity.

⇒ See the table of K-46.

*2: Changing the parameter VR enables to set to 0.01 sec. (adjustment range: 0.01~600.0 sec.).

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)

Advertising