K-39

E6581301

11

[Monitor FM/AM/pulse output function selection (1/2)]

Sensorless vector/vector with sensor ●: valid, -: invalid)

FM/AM/pulse output

Monitor output

Option No. Communicati

on No.

Option No. Communicati

on No.

Function

Unit

(Communicat

ion)

Trip retention

Speed

control

Torque

control

PM control

V/f

Reference

0

FD00

0

FE00

Output frequency

0.01Hz

●/●

●/●

1

FD02

1

FE02

Frequency command value

0.01Hz

●/●

-

2

FD03

2

FE03

Output current

0.01%

●/●

●/●

3

FD04

3

FE04

Input voltage (DC detection)

0.01%

●/●

●/●

4

FD05

4

FE05

Output voltage

0.01%

●/●

●/●

5

FD15

5

FE15

Compensated frequency

0.01Hz

●/●

●/●

6

FD16

6

FE16

Speed feedback (real-time value) *1

0.01Hz

-/●

-/●

-

-

7

FD17

7

FE17

Speed feedback (1-second filter) *1

0.01Hz

-/●

-/●

-

-

8

FD18

8

FE18

Torque

0.01%

●/●

●/●

●*2

9

FD19

9

FE19

Torque command

0.01%

-

●/●

-

-

11

FD20

11

FE20

Torque current

0.01%

●/●

●/●

-

●*2

12

FD21

12

FE21

Exciting current

0.01%

●/●

●/●

-

●*2

13

FD22

13

FE22

PID feedback value

0.01Hz

●/●

-

14

FD23

14

FE23

Motor overload factor (OL2 data)

0.01%

●/●

●/●

15

FD24

15

FE24

Inverter overload factor (OL1 data)

0.01%

●/●

●/●

16

FD25

16

FE25

Regenerative braking resistance
overload factor (OLr data)

1%

●/●

●/●

17

FD28

17

FE28

Regenerative braking resistor load factor (% ED)

1%

●/●

●/●

18

FD29

18

FE29

Input power

0.01kW

●/●

●/●

19

FD30

19

FE30

Output power

0.01kW

●/●

●/●

23

FE39

23

FE39

Optional AI2 input

*4

×

●/●

●/●

24

FE35

24

FE35

RR/S4 input

*3

×

●/●

●/●

25

FE36

25

FE36

VI/II input

*3

×

●/●

●/●

26

FE37

26

FE37

RX input

*3

×

●/●

●/●

27

FE38

27

FE38

Optional AI1 input

*4

×

●/●

●/●

28

FE40

28

FE40

FM output

1

×

●/●

●/●

29

FE41

29

FE41

AM output

1

×

●/●

●/●

30

FE51

-

-

Fixed output 1

0.01%

×

●/●

●/●

31

FA51 *5

-

-

Communication data output

1

×

●/●

●/●

32

FE50

-

-

Fixed output 2

0.01%

×

●/●

●/●

33

FE52

-

-

Fixed output 3

0.01%

×

●/●

●/●

-

-

31

FA65

Communication data output

0.01%

×

●/●

●/●

-

-

32

FE66

Attached to expansion I/O card 1 CPU
version

-

×

●/●

●/●

5.16

8.3

*1: Estimated speed is output if there is no PG feedback. If used as pulse input command with PG feedback option, frequency is displayed as in the PG feedback.
*2: Reference data *3: Analog value entered: Analog value entered × value monitored/2047 *4:Analog value entered: Analog value entered × value monitored/1023
*5: Communication no. FA51 is used for FM, FA52 for AM, FA53 for MON1 and FA54 for MON2 and pulse output, respectively.

⇒ For details, refer to Section 5.16; [Terminal FM-related parameters].

⇒ For monitor indications, refer to Section 8.3; [Set up values of monitor indication parameters].