Toshiba Tosvert VF-AS1 User Manual

Page 253

Advertising
background image

K-15

E6581301

11

[16] PID control [2/2]

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control

V/f

Reference

H

0363

Integral (I) gain

0.01~100.0

0.01/0.01

0.10

Enabled

●/●

-

*1

H

0364

PID deviation upper limit

NN

~WN Hz

0.1/0.01

*2

Enabled

●/●

-

*1

H

0365

PID deviation lower limit

NN

~WN Hz

0.1/0.01

*2

Enabled

●/●

-

*1

H

0366

Differential (D) gain

0.00~2.55

0.01/0.01

0.00

Enabled

●/●

-

*1

*1:

⇒ For details, refer to Instruction Manual (E6581329) specified in Section 6.41. *2: Inverter with a model number ending with -WN: 60.0 -WP: 50.0

[17] Speed feedback/positioning control

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control

V/f

Reference

H

0367

Process upper limit

NN

~WN Hz

0.1/0.01

*4

Enabled

-/●

-/●

-

-

*1

H

0368

Process lower limit

NN

~WN Hz

0.1/0.01

NN

Enabled

-/●

-/●

-

-

*1

H

0369

PID control waiting time

0~2400 sec.

1/1

0

Enabled

-/●

-/●

-

-

*1

H

0370

PID output upper limit

NN

~WN Hz

0.1/0.01

*4

Enabled

-

-

-

-

*1

H

0371

PID output lower limit

NN

~WN Hz

0.1/0.01

NN

Enabled

-

-

-

-

*1

H

0372

Process increasing rate (speed type

PID control)

0.1~600.0

0.1/0.1

10.0

Enabled

-

-

-

-

*1

H

0373

Process decreasing rate (speed

type PID control)

0.1~600.0

0.1/0.1

10.0

Enabled

-

-

-

-

*1

H

0375

Number of PG input pulses

12~9999

1/1

500

Disabled

●/●

-/●

-

-

*2

H

0376

Selection of number of PG input

phases

1:Single-phase input

2:Two-phase input

1/1

2

Disabled

●/●

-

-

-

*2

H

0377

PG disconnection detection

0:Deselect

1:Select (with filter)

2:Select (Detection of momentary power failure)

1/1

0

Disabled

●/●

-

-

-

*2

H

0378

Number of RP terminal input

pulses

12~9999

1/1

500

Disabled

●/●

●/●

-

-

*3

H

0381

Simple positioning completion

range

1~4000

1/1

100

Enabled

●/●

-

*2

*1:

⇒ For details, refer to Instruction Manual (E6581329) specified in Section 6.41. *2: ⇒ For details, refer to Instruction Manual (E6581319) specified in Section 6.41.

*3:

⇒ For details, refer to Instruction Manual (E6581341) specified in Section 6.41. *4: Inverter with a model number ending with -WN: 60.0 -WP: 50.0

[18] Motor constant [1/2]

Vector control

Title

Communi

cation

No.

Function

Adjustment range

Minimum

setting unit

(Panel/Communi

cation)

Default

setting

Write during

running

Speed

control

Torque

control

PM

control V/f Constant Reference

H

0400

Auto-tuning 1

0:No auto-tuning

1:Initialize motor constant (0 after execution)

2:Continue operation continued after auto-tuning (0

after execution)

3:Auto-tuning by input terminal signal

4:Motor constant auto calculation (0 after

execution)

1/1

0

Disabled

●/●

●/●

-

-

6. 22

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)

Sensorless vector/vector with sensor (●:Effective, -:Ineffective)

Advertising