11 setting frequency command characteristics, 12 preset speed operation (speeds in 15 steps) – Toshiba Tosvert VF-AS1 User Manual
Page 83

E6581301
E-17
5
5.11
Setting frequency command characteristics
H
~ H , CKH : VI/II point setting
HK
~ H , CXH : RR/S4 point setting
HK
~ H : RX point setting
H
~ H :
H
~ H :
H
~ H :
H
~ H : Point 1, 2 setting/ frequency
⇒ For details, refer to Section 7.3.
5.12
Preset speed operation (speeds in 15 steps)
UT
~ UT : Preset speed operation frequencies 1~7
H
~ H : Preset speed operation frequencies 8~15
H
~ H : Preset speed operation frequencies 1~15 operation mode
[Setting methods]
1)Run/stop
Run and stop control is experienced by the operation panel (Default setting).
Title
Function
Adjustment range
Example of setting
EOQF
Command mode
selection
: Terminal input enabled
: Operation panel input enabled (including
LED/LCD option input)
: 2-wire RS485 communication input
: 4-wire RS485 communication input
: Communication option input
Note 1: If speed commands (analog signal or digital input) are switched in line with preset speed operations, select the
terminal board using the frequency setting mode selection 1 HOQF.
⇒ Refer to 3) or Section 5.5.
Note 2: When using an optional extension LED panel or extension LCD panel, set EOQF= to enable the entry of
commands from the extension and graphic panel.
2)Preset speed frequency setting
Set the speed (frequency) of the number of steps necessary.
Setting from speed 1 to speed 7
Title
Function
Adjustment range
Default setting
UT
~UT
Preset speed operation
frequencies 1~7
NN
~WN
Setting from speed 8 to speed 15
Title
Function
Adjustment range
Default setting
H
~H
Preset speed operation
frequencies 8~15
NN
~WN
Example of preset speed contact input signal
It sets up, when using the optional circuit board.
• Function
A maximum of 15 speed steps can be selected just by switching an external contact signal. Preset speed
frequencies can be programmed anywhere from the lower limit frequency NN to the upper limit frequency WN.
• Function
These parameters adjust the output frequency according to the externally applied analog signal (0~10Vdc
voltage, 4(0)~20mAdc current) and the entered command for setting an external contact frequency.