6 selecting control mode – Toshiba Tosvert VF-AS1 User Manual

Page 77

Advertising
background image

E6581301

E-11

5

5.6

Selecting control mode

RV

: V/f control mode selection

[Parameter setting]

Title

Function

Adjustment range

Default setting

RV

V/f control mode selection



: Constant torque characteristics



: Voltage decrease curve



: Automatic torque boost



: Sensorless vector control 1



: Sensorless vector control 2



: V/f 5-point setting



: PM control



: PG feedback vector control 1



: PG feedback vector control 2



1) Constant torque characteristics (Normal way of use)

Setting of V/f control mode selection RV= (Constant torque characteristics)

This is applied to loads with equipment like conveyors and cranes that require the same torque at low speeds as at
rated speeds.

Base frequency voltage 1

XNX

Output frequency [Hz]

XD

Base frequency XN

0

Ou
tp

u

t vol
ta

ge

[V]/[%]

* To increase the torque further, increase the setting value of the manual torque boost parameter XD.

⇒ For more details, refer to Section 5.7.

• Function

With “VF-AS1,” the V/f controls shown below can be selected.
0: Constant torque characteristics
1: Voltage decrease curve
2: Automatic torque boost *1
3: Sensorless vector control 1 *1
4: Sensorless vector control 2
5: V/f 5-point setting
6: PM control
7: PG feedback vector control 1
8: PG feedback vector control 2

(*1) “Automatic control” parameter automatically sets this parameter and auto-tuning 1 at a time.