6 selecting control mode – Toshiba Tosvert VF-AS1 User Manual
Page 77

E6581301
E-11
5
5.6
Selecting control mode
RV
: V/f control mode selection
[Parameter setting]
Title
Function
Adjustment range
Default setting
RV
V/f control mode selection
: Constant torque characteristics
: Voltage decrease curve
: Automatic torque boost
: Sensorless vector control 1
: Sensorless vector control 2
: V/f 5-point setting
: PM control
: PG feedback vector control 1
: PG feedback vector control 2
1) Constant torque characteristics (Normal way of use)
Setting of V/f control mode selection RV= (Constant torque characteristics)
This is applied to loads with equipment like conveyors and cranes that require the same torque at low speeds as at
rated speeds.
Base frequency voltage 1
XNX
Output frequency [Hz]
XD
Base frequency XN
0
Ou
tp
u
t vol
ta
ge
[V]/[%]
* To increase the torque further, increase the setting value of the manual torque boost parameter XD.
⇒ For more details, refer to Section 5.7.
• Function
With “VF-AS1,” the V/f controls shown below can be selected.
0: Constant torque characteristics
1: Voltage decrease curve
2: Automatic torque boost *1
3: Sensorless vector control 1 *1
4: Sensorless vector control 2
5: V/f 5-point setting
6: PM control
7: PG feedback vector control 1
8: PG feedback vector control 2
(*1) “Automatic control” parameter automatically sets this parameter and auto-tuning 1 at a time.