9. OPERATION DESCRIPTION

9-1. Outline of Air Conditioner Control

This air conditioner is a capacity-variable type air

conditioner, which uses AC motor both the indoor

fan motor and the outdoor fan motor. And the capacity-

proportional control compressor which can change the

motor speed in the range from 22 to 83 rps is

mounted. The AC motor drive circuit is mounted to the

indoor unit. The compressor and the inverter is mounted

to the outdoor unit.
The entire air conditioner is mainly controlled by the

indoor unit controller.
The indoor unit controller drives the indoor fan motor

based upon command sent from the remote controller,

and transfers the operation command to the outdoor

unit controller.
The outdoor unit controller receives operation com-

mand from the indoor unit side, and controls the

of the

compressor motor, the outdoor unit controller

controls

speed of the compressor motor by controlling

And then, the outdoor unit controller transfers reversely

the operating status information of the outdoor unit to

control the indoor unit controller.

As the compressor adopts four -pole brushless
DC motor , the frequency of the supply power
from in verter to compressor is two-times cycles
of the actual number of revolution.

1. Role of indoor unit controller

The indoor unit controller judges the operation

commands from the remote controller and assumes

the following functions.
• Judgment of suction air temperature of the indoor

heat exchanger by using the indoor temp. sensor.

(TA sensor)

• Judgment of the indoor heat exchanger tempera-

ture by using heat exchanger sensor (TC sensor)

(Prevent-freezing control, etc.)

• Louver motor control
• Indoor fan motor operation control
• LED (Light Emitting Diode) display control
• Transferring of operation command signal (Serial

signal) to the outdoor unit

• Reception of information of operation status

(Serial signal including outside temp. data) to the

outdoor unit and judgment/display of error

2. Role of outdoor unit controller

Receiving the operation command signal (Serial

signal) from the indoor unit controller, the outdoor

unit performs its role.

• Compressor operation control

• 4-way valve control

Operations followed to judgment

of serial signal from indoor side

.

• Detection of inverter input current and current

release operation

• Over-current detection and prevention operation

to IGBT module (Compressor stop function)

• Compressor and outdoor fan stop function when

serial signal is off (when the serial signal does not

reach the board assembly of outdoor control by

trouble of the signal system)

• Transferring of operation information (Serial

signal) from outdoor unit controller to indoor unit

controller

• Detection of outdoor temperature and operation

revolution control

• Defrost control in heating operation (Temp.

measurement by outdoor heat exchanger and

control for 4-way valve and outdoor fan)

3. Contents of operation command signal

(Serial signal) from indoor unit controller to
outdoor unit controller

The following three types of signals are sent from

the indoor unit controller.
• Operation mode set on the remote controller
• Compressor revolution command signal defined

by indoor temperature and set temperature

(Correction along with variation of room tempera-

ture and correction of indoor heat exchanger

temperature are added.)

• Temperature of indoor heat exchanger
• For these signals ([Operation mode] and [Com-

pressor revolution] indoor heat exchanger tem-

perature), the outdoor unit controller monitors the

input current to the inverter, and performs the

followed operation within the range that current

does not exceed the allowable value.

4. Contents of operation command signal

(Serial signal) from outdoor unit controller
to indoor unit controller

The following signals are sent from the outdoor unit

controller.
• The current operation mode
• The current compressor revolution
• Outdoor temperature
• Existence of protective circuit operation

For transferring of these signals, the indoor unit

controller monitors the contents of signals, and

judges existence of trouble occurrence.
Contents of judgment are described below.
• Whether distinction of the current operation

status meets to the operation command signal

• Whether protective circuit operates

When no signal is received from the outdoor

unit controller, it is assumed as a trouble.

output voltage of the inverter and switching timing of

the supply power (current transfer timing) so that motors

drive according to the operation command.

FILE NO. SVM-07008

outdoor fan motor. Besides detecting revolution position