5. judgement of trouble by every symptom – Toshiba RAS-10SKV-A User Manual

Page 66

Advertising
background image

– 65 –

Operation

Measure

Item by symptoms

Check item

Conceivable principle

cause

Parts

(D01 ~ D04,

C03, T101

and IC12 are

defective.

Be sure to disconnect the motor connector CN10 after shut off the power supply, or it will be a cause of
damage of the motor.

(1) Power is not turned on (Does not operate entirely)

3

FILE NO. SVM-07008

11-5. Judgement of Trouble by Every Symptom

11-5-1. Indoor unit (Including remote controller)

Turn off power

supply once, and 5

second later, turn it

on again.

Is OPERATION

lamp blinking?

NO

YES

NO

NO

YES

YES

Is it possible to

turn on power

supply by

pressing

[ ] button

on remote

control?

Does

transmission

mark on

remote control

flash normally,

and is its signal

transmitted

properly?

Remote control is

defective.

Refer to (5)

Remote Control."

Is fuse (F01)

of indoor control

board blown?

Is voltage

(DC 12V or 5V)

indicated on

rear of indoor

control board

normal?

Microcomputer

is defective.

Replace main

P.C. board.

Refer to

<Primary check>

or this problem

is one step short

of power P.C.

Is the

voltage

across C03

mesured

YES

YES

NO

NO

NO

NO

YES

Does

fan motor

connector

between 1

and

short-circuit?

Unit operates

normally.

board block.

Are DC 5V,

DC 12V

supplied

to main

P.C. board?

Turn off breaker

once and turn it

on again after

removing motor.

Regulator IC

(IC12) or T101

are defective

Replace motor

.

NO

NO

YES

YES

YES

Are DC 5V,

or DC 12V

supplied

to main

P.C. board?

"Troubleshooting for

DC 310V~340V?

Advertising
This manual is related to the following products: