– 57 –

FILE NO. SVM-07008

<Stripping length of connection cable>

CAUTION

Wrong wiring connection may cause some
electrical parts burn out.

Be sure to comply with local codes on running
the wire from indoor unit to outdoor unit (size of
wire and wiring method etc).

Every wire must be connected firmly.

This installation fuse (25A

Model

Power source 50 Hz, 220 - 240 V Single phase
Maximum

8A

running current
Installation fuse

25A

rating

Power cord

H07RN-F or 245 IEC66 (1.5 mm

2

or more)

RAS-10SKV

) must

be used for the power supply line of this air

conditioner.

If incorrect or incomplete wiring is carried out, it

will cause an ignition or smoke.

Prepare the power supply for exclusive use with

the air conditioner.

This product can be connected to the mains.

Connection to fixed wiring: A switch which

disconnects all poles and has a contact

separation of at least 3 mm must be incorporated

in the fixed wiring.

NOTE: Connecting cable

• Wire type: More than H07RN-F or 245 IEC66

(1.0 mm

2

or more)

<Packed valve handling precautions>

Open the valve stem all the way out; but do not try

to open it beyond the stopper.

Securely tighten the valve stem cap with torque in

the following table:

Fig. 10-3-8

10

-3-4. Wiring connection

1. Remove the valve cover from the outdoor unit.

2. Connect the connecting cable to the terminal as

identified with their respective matched numbers on

the terminal block of indoor and outdoor unit.

3. When connecting the connecting cable to the

outdoor unit terminal, make a loop as shown in the

installation diagram of indoor and outdoor unit, to

prevent water coming in the outdoor unit.

4. Insulate the unused cords (conductors) from any

water coming in the outdoor unit. Proceed them so

that they do not touch any electrical or metal parts.

4 mm

He

xagonal wrench

is required.

Gas side

30 to 42 N·m

(∅9.52 mm)

(3.0 to 4.2 kgf·m)

Liquid side

16 to 18 N·m

(∅6.35 mm)

(1.6 to 1.8 kgf·m)

Service port

9 to 10 N·m

(0.9 to 1.0 kgf·m)

Fig.

10-3-8

Terminal block

Connecting cable

Power cord

Earth line

Earth line

Connecting cable

Power cord

10

10

10

10

45 40

60 50

L N

1 2 3