File no. svm-7008 – Toshiba RAS-10SKV-A User Manual

Page 65

Advertising
background image

– 64 –

FILE NO. SVM-7008

Block distinction

Operation of diagnosis function

Judgment and action

Check

Block

Check

Cause of operation

Air conditioner

Remarks

code

code

status

Inverter over-current
protective circuit operates.
(Short time)

Position-detect circuit error
or short-circuit between
windings of compressor

Current-detect circuit error

Being out of place,
disconnection or short-
circuit of outdoor temp.
sensor

Disconnection or short-
circuit of discharge temp.
sensor

Outdoor fan drive system
error

Outdoor heat exchanger
temp. sensor error

Compressor drive output
error, Compressor error
(lock, missing, etc.),
Break down

Return serial signal has
been sent when operation
started, but it is not sent
from halfway.
(1) Compressor thermo.

operation
Gas shortage
Gas leak

(2) Instantaneous power

failure

Compressor does not
rotate. (Current protective
circuit does not operate
when a specified time
passed after compressor
had been activated.)

Discharge temp. exceeded
117°C

Break down of compressor

Four-way valve inverse error
(TC sensor value lowered
during heating operation.)

All off

All off

All off

All off

All off

All off

Operation
continues.

All off

Operation
continues.

All off

All off

All off

Operation
continues.

Displayed when
error is detected.

Displayed when
error is detected.

Displayed when
error is detected.

Displayed when
error is detected.

Displayed when
error is detected.

Displayed when
error is detected.

–––

Displayed when
error is detected.

Flashes when
trouble is
detected on
return serial
signal, and
normal status
when signal is
reset.

Displayed when
error is detected.

Displayed when
error is detected.

Displayed when
error is detected.

–––

Even if trying operation again, all
operations stop immediately. :
Replace P.C. board.

1. Even if connecting lead wire of

compressor is removed, position-
detect circuit error occurred.
: Replace P.C. board.

2. Measure resistance between

wires of compressor, and perform
short circuit. : Replace
compressor.

Even if trying operation again, all
operations stop immediately. :
Replace P.C. board.

1. Check outdoor temp. sensors

(TE, TS).

2. Check P.C. board.

1. Check discharge temp. sensor (TD).
2. Check P.C. board.

Position-detect error, over-current
protective operation of outdoor fan
drive system, fan lock, etc. :
Replace P.C. board or fan motor.

1. Check outdoor heat exchanger

temp. sensor (TE).

2. Check P.C. board.

When 20 seconds passed after
startup, position-detect circuit error
occurred. : Replace compressor.

1. Repeat Start and Stop with

interval of approx. 10 to 40
minutes. (Code is not displayed
during operation.)
Supply gas. (Check also gas leak.)

2. Unit operates normally during

check.
If return serial signal does not
stop between indoor terminal
block,

2

and

3

replace inverter

P.C. board.
If signal stops between indoor
terminal block,

2

and

3

replace

indoor P.C. board.

1. Trouble on compressor
2. Trouble on wiring of compressor

(Missed phase)

1. Check discharge temp. sensor (TD).
2. Degassing
3. Trouble on P.M.V.

1. Check power voltage. (220-240 V

+10%)

2. Overload operation of

refrigeration cycle
Check installation condition
(Short-circuit of outdoor diffuser.)

1. Check 4-way valve operation.

Ondoor
P.C.
board

Not
displayed

Ondoor
P.C.
board

Others
(including
compres-
sor)