FILE NO. SVM-07008

(3) Checking procedure.

Table 11-6-1

No.

1

2

3

4

5

6

Procedure

1. Application of shock voltage.

Overload by short-circuit of the

parts.

1. AC power cord is defective.

Poor contact of the terminal plate.

2. Capacitor (C121) is defective.

Line filter (L01) is defective.

Capacitor (C03) is defective.

Diode (D01,D02,D03, or D04)

is defective.

Defective indicator, or poor

housing assembly. (CN21)

1.The temperature of the indoor

heat exchanger is abnormally

lower.

2.Poor contact of the heat

exchanger sensor. (The connector

is disconnected.) (CN62)

3.Heat exchanger sensor, main

P.C. board are defective. (Refer to

4.Main P.C. board is defective.

1. The temperature of the heat

exchanger is abnormally high.

2. The heat exchanger sensor

connector has short-circuit. (CN62)

3. The heat exchanger sensor is

defective.

4. P.C. board is defective.

1. Poor contact of the motor

connector.

2. Fan motor is defective

1. Is the fuse blown?

Voltage check

1.Between F01 and CN01(pin 1)

(AC 220 ~ 240 V)

2.Between + and −

of C03

DC310~DC340V

3. Between

5V

and

GND

4. Between

12V

and

GND

1. All indicators light for 3 sec..

2. Indicators do not indicate normally

after approximate 3 sec..

1. Compressor does not operate.

2. OPERATION lamp blinks.

1. Compressor does not operate.

2. OPERATION lamp blinks.

1.Motor does not rotate. (The key

operation is accepted.)

2. The Motor rotates, but it vibrates

too much.

Shut off the power supply and

remove the P.C. board assembly

from the electronic parts base.

Remove the connecting cable from

the terminal block.

Remove the connector for the motor,

and turn the power on.

If the OPERATION lamp blinks

(0.5 sec. : ON, 0.5 sec. : OFF) when

the power turning on, the checking

points described as 1-4 of right

column are not necessary to

perform.

Start the operation with the system

which the time of the restart delay

timer is shortened.

Make the operation status by

pressing once the [ ] button.

1.The time of the restart delay timer

is shortened.

2.Cool operation

3.Air volume [AUTO]

4.Make the setting temperature lower

enough than room temperature.

5. Continuous operation.

The status of No. 4 is continued, and

make the following condition.

1.Heat operation

2.Make the setting temperature

higher enough than room

temperature.

Turn the power on after connecting

the motor connector. Start the

operation with the following

condition.

1.Operation [Cooling]

2.Airflow [High fan]

3.Continuous operation

Check Point (Symptom)

}

Causes

– 74 –

3. T101 is defective.