Item

Operation flow and applicable data, etc.

Description

6. Defrost control

(Only in heating
operation)

(This function removes frost adhered to the outdoor
heat exchanger.)

The temperature sensor of the outdoor heat ex-
changer (Te sensor) judges the frosting status of the
outdoor heat exchanger and the defrost operation is
performed with 4-way valve reverse defrost system.

The necessity of defrost operation is
detected by the outdoor heat exchanger
temperature. The conditions to detect the
necessity of defrost operation differ in A,
B, or C zone each. (Table 1)

<Defrost operation>

• Defrost operation in A to C zones

1) Stop operation of the compressor for

20 seconds.

2) Invert (OFF) 4-way valve 10 seconds

after stop of the compressor.

3) The outdoor fan stops at the same time

when the compressor stops.

4) When temperature of the indoor heat

exchanger becomes 38°C or lower,
stop the indoor fan.

<Finish of defrost operation>

• Returning conditions from defrost

operation to heating operation

1) Temperature of outdoor heat exchanger

rises to +8°C or higher.

2) Temperature of outdoor heat exchanger

is kept at +5°C or higher for 80 seconds.

3) Defrost operation continues for

15 minutes.

<Returning from defrost operation>
1) Stop operation of the compressor for

approx. 50 seconds.

2) Invert (ON) 4-way valve approx. 40

seconds after stop of the compressor.

3) The outdoor fan starts rotating at the

same time when the compressor starts.

Table 1

* The minimum value of Te sensor 10 to 15 minutes

after start of operation is stored in memory as Te0.

–5˚C

0’

10’ 15’

27’40”

34’

–7˚C

–20˚C

Operation time
(Minute)

Start of heating operation

*

Outdoor heat e

xchanger temper

ature

C zone

A zone

B zone

A zone

B zone

C zone

When Te0 - TE

2.5 continued for 2 minutes in A zone,

defrost operation starts.

When the operation continued for 2 minutes in B zone,
defrost operation starts.

When Te0 - TE

3 continued for 2 minutes in C zone,

defrost operation starts.