How to diagnose the trouble – Toshiba RAS-10SKV-A User Manual

Page 60

Advertising
background image

– 59 –

FILE NO. SVM-07008

Inverter cover

P. C. board
(Soldered surface)

Discharging position
(Discharging period
10 seconds or more)

Plug of
soldering
iron

11. HOW TO DIAGNOSE THE TROUBLE

The pulse modulating circuits are mounted to both
indoor and outdoor units. Therefore, diagnose troubles
according to the diagnosis procedure as described
below. (Refer to the check points in servicing written
on the wiring diagrams attached to the indoor/outdoor
units.)

Table 11-1

No. Troubleshooting Procedure

1 First Confirmation

2 Primary Judgment

3 Judgment by Flashing LED

of Indoor Unit

4 Self-Diagnosis by Remote Control

5 Judgment of Trouble by

Every Symptom

6 How to Check Simply the Main Parts

Fig. 11-1

NOTE:
A large-capacity electrolytic capacitor is used in the
outdoor unit control (inverter). Therefore, if the power
supply is turned off, charge (charging voltage DC280V)
remains and discharging takes a lot of time. After
turning off the power source, if touching the charging
section before discharging, an electrical shock may be
caused. Discharge the electrolytic capacitor completely
by using soldering iron, etc.

<Discharging method>
(1) Remove the inverter cover (plating) by opening four

mounting claws.

(2) As shown below, connect the discharge resistance

(approx. 100

40W) or plug of the soldering iron to

voltage between + – terminals of the C14
(“CAUTION HIGH VOLTAGE 380 V” is indicated.)
electrolytic capacitor (760

µ

F/400 V) on P.C. board,

and then perform discharging.

10-1. First Confirmation

10-1-1. Confirmation of power supply

Confirm that the power breaker operates (ON)
normally.

10-1-2. Confirmation of power voltage

Confirm that power voltage is AC 220-240 V ± 10%. If
power voltage is not in this range, the unit may not
operate normally.

Advertising
This manual is related to the following products: