Toshiba RAS-10SKV-A User Manual

Page 68

Advertising
background image

FILE NO. SVM-07008

– 67 –

(3) Only the indoor fan does not operate.

Replace the fan motor.

YES

NO

NO

YES

YES

NO

NO

YES

YES

YES

NO

NO

NO

YES

Does the fan stop in

no operating status?

Control P.C. board is defective.

Start the operation

with low fan setting

in cool operation.

Does AC 120 V

or higher voltage apply

to between red and black

lead of fan motor?

Does the fan rotate?

Change the setting of

cooling to high fan.

Operation

stops

Shut off the power supply.

Motor control circuit failure

(IC31, D301) or 12 V

switching module failure (T101).

Does the cross flow

fan rotate normally?

Is the rotation signal (DC+5 V

0 V)

output between

2

(gray lead wire)

and

3

(brown lead wire) of the motor

connector (CN11) when rotating the

cross flow fan by hand in no operating

status? (1 pulse/one turn)

Turn on the power supply.

Repair the

bearing of

the fan.

Turn the power supply.

Shut off the

power supply once.

Does connecting

terminal, connecting

cable or power supply

cord completely?

Does not found the short

wire about connecting

cable and power cord?

Does the fan speed

become higher?

Replace connecting the

cable (or power cord)

and terminal

block.

Replace the P.C. board.

Replace the P.C. board.

Normal

Replace the control

P.C. board.

<Check procedure>