P. 59-c12), P. 59-c13), P. 59-c14) – Vax M-9000 User Manual

Page 59: P. 59-c15), P. 59-c16)

Advertising
background image

Select the control input terminal to switch the ANC inputs* to be monitored.
Selecting the terminal overwrites the previously set function on it if there is.

Each time the designated terminal is closed, the ANC inputs to be monitored are switched in numerical order
from ANC input 1.

* ANC inputs are the input channels of AN-001T Ambient Noise Sensor Input module. One AN-001T module

has 2 input channels. When 2 AN-001T modules are mounted, the AN-001T's inputs in the slot with smaller
number correspond to ANC Input channels 1 and 2, and another's inputs in another slot to ANC Input
channels 3 and 4.

59

(C12) ANC monitor switching ON/OFF setting

A N C M O N

S E L E C T =

O N

If there are 2 or more ANC inputs, set whether or not ANC inputs to be monitored are switched.

OFF (default), ON

Setting Range

(C13) Monitor switching control input terminal setting (When the ANC monitor switching is set to ON)

M O N

S E L E C T

C I N 0 1

CIN01 – 04, CIN01 – 12 when C-001T is used (default: CIN01)

Setting Range

(C14) Interlock output control setting (When the ANC monitor switching is set to ON)

M O N

S E L

S Y N C

O N

Perform ON/OFF setting for the function that closes the control output terminal in synchronization with the
control input terminal closure of the set number.

OFF (default), ON

Setting Range

(C15) Monitored ANC input channel selection
(When the ANC monitor switching is set to ON, and the interlock output control to ON)

S E L E C T S Y N C

A N C 1

Select the ANC input channel. Each channel for which the monitor function is set to ON can be selected.

ANC 1 – 4 (Only ANC input channels for which the monitor function is ON)

Setting Range

(C16) Interlock output terminal setting
(When the ANC monitor switching is set to ON, and the interlock output control to ON)

S E L E C T S Y N C

C O U T 0 1

Set the control output terminal which is closed in synchronization with switching to the monitored ANC input
channel.
Assigning the function to this terminal overwrites the previously set function on it if there is.

COUT01 – 04, COUT01 – 12 when C-001T is used (default: COUT01)

Setting Range

Advertising