Charge algorithm graph, Charge algorithm definitions, Figure b-1 – Xantrex Technology MS2000 User Manual

Page 109: Voltage flooded (or wet) gel agm, Current flooded (or wet) gel agm, Time flooded (or wet) gel agm

Advertising
background image

Battery Charging Reference for the Main Charger

975-0125-02-01

B–5

Charge Algorithm Graph

Charge Algorithm Definitions

Table B-1 Battery Defaults

Figure B-1 Three-Stage Charging Profile

Voltage

Flooded (or wet) Gel

AGM

V

A

Absorption Voltage (VDC)

14.4

14.4

14.3

V

G

Gassing Voltage (VDC)

13.5

13.8

13.45

V

F1

Float Voltage (VDC)

13.5

13.8

13.45

V

F2

Float Exit Voltage (VDC)

12.5

12.5

12.5

V

E

Equalize Voltage (VDC)

15.5

NA

NA

Current

Flooded (or wet) Gel

AGM

I

B

Bulk Current (ADC)

20% Ah

20% Ah

20% Ah

I

H

Absorption Exit Current (ADC)

2% Ah

2% Ah

2% Ah

I

E

Equalize Current (ADC)

10% Ah

NA

NA

Time

Flooded (or wet) Gel

AGM

T

A

Absorption Timeout (hours)

6

6

6

T

CV

Constant Voltage Absorption Timeout (hours)

1

1

1

I

H

I

B

V

F2

V

F1

V

G

V

A

Float

Time

T

CV

T

A

T

F

Bulk

Absorption