Troubleshooting

975-0125-02-01

4–7

Table 4-3 provides a detailed description of the warning messages and solutions.

Table 4-3 Warning Messages

Warning

Number Message

Warning

Type

Cause

Solution

W0

FET1 over-temp.
Check airflow
around it.

Automatic FET1

Over

Temperature Warning

Ensure adequate ventilation
around the MS2000. Reduce
the AC loads.

W1

FET2 over-temp.
Check airflow
around it.

Automatic

FET2 Over
Temperature Warning

Ensure adequate ventilation
around the MS2000. Reduce
the AC loads.

W2

Bulk cap. over-temp.
Check airflow
around it.

Automatic

DC Bulk Capacitor
Over Temperature
Warning

Ensure adequate ventilation
around the MS2000. Reduce
the AC loads.

W3

Transf’r over-temp.
Check airflow
around it.

Automatic

Transformer Over
Temperature Warning

Ensure adequate ventilation
around the MS2000. Reduce
the AC loads.

W4

Battery over-temp.
Check battery
settings.

Automatic

Battery Over
Temperature Warning

Check battery voltage and
battery cable connections. Stop
charging, if necessary. Check
for excessive ambient
temperature and adequate
ventilation in the battery
compartment

W5

Over-temperature.
Check airflow
around it.

Automatic

Ambient Over
Temperature Warning

Ensure adequate ventilation
around the MS2000. Reduce
charge rate or AC load.

W6

Too many AC loads.
Turn some off.

Automatic

AC Overload Warning
(AC OUPUT)

Turn off some AC loads.

W7

You have enabled
system restart after
faults.

Automatic

Auto Restart After
Fault Feature Enabled.
(This parameter is not
accessible through the
System Control Panel.
In the future, this
feature may be
configurable with
advanced panels.)

If in invert mode, the unit may
start up unexpectedly.

W8

You have enabled
battery equalization.
See manual.

Automatic

Equalization Enabled
Warning

Make sure voltage sensitive
loads are disconnected from
batteries.