Fault number message fault type cause solution – Xantrex Technology MS2000 User Manual

Page 94

Advertising
background image

Troubleshooting

4–12

975-0125-02-01

F15

Input AC too low.
Check source, clear
fault, try again.

Automatic

AC Under Voltage
Shutdown (AC Line 2
input)

Not applicable to MS2000.

F16

AC input frequency
problem. Check gen
for overspeed.

Automatic

AC Over Frequency
Shutdown (AC Line 1
input)

Clear the fault and attempt
restart. Check AC input
frequency. Check and adjust
AC input high frequency
setting.

F17

AC input frequency
problem. Check gen
for underspeed.

Automatic

AC Under Frequency
Shutdown (AC Line 1
input)

Clear the fault and attempt
restart. Check AC input
frequency. Check and adjust
AC input low frequency
setting.

F18

AC input frequency
problem. Check gen
for overspeed.

Automatic

AC Over Frequency
Shutdown (AC Line 2
input)

Not applicable to MS2000.

F19

AC input frequency
problem. Check gen
for underspeed.

Automatic

AC Under Frequency
Shutdown (AC Line 2
input)

Not applicable to MS2000.

F23

Reset the MS2000. If
problem persists, call
customer service.

Escalating
Auto Fault.
Must occur
3 times in
30 seconds
before
becoming
a manual
fault.

AC Over Voltage
Shutdown (Inverter
AC output)

Clear the fault and attempt
restart. If problem persists, call
customer service.

F24

Reset the MS2000. If
problem persists, call
customer service.

Escalating
Auto Fault.
Must occur
3 times in
60 seconds
before
becoming
a manual
fault.

AC Under Voltage
Shutdown (Inverter
AC output)

Clear the fault and attempt
restart. If problem persists, call
customer service.

Table 4-4 Fault Messages

Fault

Number Message

Fault

Type

Cause

Solution