Fault number message fault type cause solution – Xantrex Technology MS2000 User Manual

Page 95

Advertising
background image

Troubleshooting

975-0125-02-01

4–13

F25

Reset the MS2000. If
problem persists, call
customer service.

Escalating
Auto Fault.
Must occur
3 times in
30 seconds
before
becoming
a manual
fault.

Auxiliary Power
Supply Over Voltage
Shutdown

Clear the fault and attempt
restart. If problem persists, call
customer service.

F26

Reset the MS2000. If
problem persists, call
customer service.

Escalating
Auto Fault.
Must occur
3 times in
30 seconds
before
becoming
a manual
fault.

Auxiliary Power
Supply Under Voltage
Shutdown

Clear the fault and attempt
restart. If problem persists, call
customer service.

F29

Reset the MS2000. If
problem persists, call
customer service.

Manual AC

Backfeed

Shutdown

Clear the fault and attempt
restart. If problem persists, call
customer service.

F30

is too cold and has
shut down. See
guide.

Manual Battery

Under

Temperature Fault

Clear the fault and attempt one
restart. Try restart again when
ambient temperature is warmer
or gently warm the battery.

F31

Echo Charger fault.
Disable Echo
Charger.

Escalating
Automatic
Faults

Echo Charger Short
Circuit

Check wiring from Echo
Charger to engine battery.

F32

Echo Charger
disabled. Reverse
battery polarity.

Manual

Echo Charger Reverse
Polarity

Check Echo Charger
connection to the battery.

F33

Echo Charger input
over voltage.

Automatic

Echo Charger Input
Over Voltage

Clear the fault and attempt
restart. Ensure battery voltage
is 10–16 VDC at MS2000
terminals. Check all other
charging source outputs,
battery cables.

Table 4-4 Fault Messages

Fault

Number Message

Fault

Type

Cause

Solution