Hi ac volt, Hi ac freq, Hi ac volt –26 hi ac freq –26 – Xantrex Technology MS2000 User Manual

Page 80

Advertising
background image

Configuration

3–26

975-0125-02-01

Outcome

The lower frequency of voltage that will be qualified as “good” by the inverter/
charger can be varied.

Hi AC Volt

Full name

Hi AC transfer voltage (AC over voltage level)

Configurable setting

This setting lets you adjust the voltage above which the inverter/charger no longer
qualifies AC as “good” and attempts to transfer to Invert.

When to use

This setting lets you adjust the AC parameters when AC supply is outside the
upper voltage range required for electrical equipment.

Outcome

The upper level of voltage that will be qualified as “good” by the inverter/charger
can be varied.

Hi AC Freq

Full name

Hi AC transfer frequency (AC over frequency level)

Configurable setting

This setting lets you adjust the frequency at which the MS2000 no longer qualifies
AC as “good” and attempts to transfer to Invert.

When to use

This setting lets you adjust the AC parameters when the AC supply is outside the
higher frequency range required for electrical equipment.

Outcome

The higher frequency of voltage that will be qualified as “good” by the inverter/
charger can be varied.

Hi AC Volt

[135V]

Range of values

Increment

Default

120 to 145 VAC

1 volt

135 VAC

Hi AC Freq

[65Hz]

Range of values

Increment

Default

62 to 70 Hz

1 Hz

65 Hz