The XM2-300HP powers signal processing equipment in cable television and broadband LAN

distribution systems. The XM2-300HP provides a critical load with current-limited, regulated AC power

that is free of spikes, surges, sags and noise.
During AC line operation, AC power entering the power supply is regulated by a multi-tap transformer

at the required output voltage. The regulated voltage is connected to the load via the output

connectors, and some power is directed to the battery charger to maintain a float charge on the

batteries.
When the incoming AC line voltage significantly deviates from normal, the XM2-300HP inverter

module automatically switches to standby operation and maintains power to the load. In standby

mode, the XM2-300HP powers the load until the battery voltage reaches a low-battery cutoff point.
When utility power returns, the XM2-300HP transformer module waits a short time (approximately 20

to 40 seconds) for the utility voltage and frequency to stabilize and then initiates a smooth, in-phase

transfer back to AC line power. Once the transfer is complete, the battery charger recharges the

batteries in preparation for the next event.

1.0 Introduction to the XM2-300HP

The XM2-300HP contains an impressive list of features, including:

Smart Display

Built-in self test (with inverter diagnostics)

Battery test (advanced battery diagnostics)

Protective Interface Module (PIM) (factory installed option)

A high efficiency transformer

Improved Status menus

Communications menu with DOCSIS

®

parameters

Using the Smart Display, the operator can view all of the power supply’s operating parameters.

Automatic scrolling (AUTO-SCROLL) is always active so there is no need to press any buttons to

view the power supply’s status or system parameters. In place of operating parameters, active alarms

automatically indicate in the Smart Display so the operator can immediately see what fault is being

detected. Troubleshooting tips automatically display in the

Alarm menu screen.

The built-in metering circuits measure voltage and current, without the need for external test

equipment.

The Protective Interface Module (PIM) option allows the XM2-300HP CableUPS to provide

programmable current limits for two output channels.

The duration of battery-backed standby operation depends upon the type and number of batteries and the

load on the power supply.