Alpha Technologies XM2-300CE-HP User Manual

Page 49

Advertising
background image

4. 0 Operation, continued

4.6

Smart Display Glossary, continued

Overcurrent Tolerance Period: An output overcurrent condition is tolerated on either of

the PIM outputs for this amount of time. When this delay expires, the output protection relay

disables the output. This parameter is only visible when the Protective Interface Module (PIM)

is installed.
Power Supply priority: The Power Supply Priority is set by the service provider and identifies

the priority level of the unit at time of service if multiple service calls are issued simultaneously.
Reset Output 1, Reset Output 2: Programming this feature resets the corresponding output

in the event one or both outputs are tripped. Upon clearing the alarm, either manually or via

an automatic retry, the output(s) remain on. This parameter is only visible when the Protective

Interface Module (PIM) is installed.
Retry Delay: PIM option output fault retry interval timer. This is the period of time between

each attempt to restart an output connection. A value greater than 600 seconds disables the

automatic retry function. This parameter is only visible when the Protective Interface Module

(PIM) is installed.
Retry Limit: PIM fault retry count limit. This is the number of times the XM2-300HP attempts

to restart an output connection at the frequency specified by Retry Delay. Once the retry limit

is exceeded, attempts to restart the feeder occur indefinitely, once every 30 minutes. This

parameter is only visible when the Protective Interface Module (PIM) is installed.
Set Defaults: When programmed to YES, all the programmable data levels (except DEVICE

ADDRESS) are reset to the original factory settings.
Self Test: When programmed to YES, the XM2-300HP automatically starts a 10 second self-

test 30 seconds after initial start up
Standby Events: XM2-300HP standby events counter. This does not include self test events.

Use the Setup Menu to reset Standby Events to zero.
Standby Time: The total amount of time the XM2-300HP has operated in standby mode. This

does not include self test time and represents the sum total number of minutes of AC line failure

since the last time the counter was reset. Use the Setup Menu to reset Standby Time to zero.

Technician ID number: The Technician ID number is determined by the service provider and is

entered to record the service history of the unit.
Test Countdown: The number of days remaining before the next scheduled automatic self-test

initiates. This variable is programmable and you can select the day that the autotest sequence

will begin. This counter has no effect if test interval is set to 0.
Test Duration: Automatic self test duration timer. This sets the number of minutes the XM2-

300HP performs a battery maintenance cycle test. This timer applies to automatically or

manually initiated tests.
Test Discharge percentage: The depth of discharge allowed during a battery/inverter test and

is based on battery capacitance and power supply load.
Test Inhibit: Becomes active when programmed by the operator (or when the unit runs in

inverter mode for more than 5 minutes). The XM2-300HP delays the start of a scheduled self

test for seven days if the test countdown is less than seven days (See Section 4.4, Automatic

Performance Test for complete details).
Test Interval: Automatic self test control timer. The number of days between battery

maintenance cycle tests. Set this value to zero to disable automatic self test.
Total Run Time: The amount of time (in days) the power supply has functioned in any mode of

operation. This is not a resetable value.

Resetting factory defaults does not clear Standby Events or Standby Time.

NOTE:

49

017-877-B1-001 Rev. A

Advertising
This manual is related to the following products: