Utility Power Connection Notes

UL and NEC require that a service disconnect switch (UL listed) be provided by the installer and be connected

between the power source and the ALPHA power supply. Connection to the power supply must include an

appropriate service entrance weather head.

Connecting to the utility should be performed only by qualified service personnel and in compliance with local

electrical codes. Connection to utility power must be approved by the local utility before installing the power

supply.

ATTENTION:

In order to accommodate the high-inrush currents normally associated with the start-up of active load

transformers (400 Amp, no-trip, first-half cycle), either a “high-magnetic” or an HACR (Heating, Air

Conditioning, Refrigeration) trip breaker must be used. Do not replace these breakers with a conventional

service entrance breaker. Alpha recommends ONLY Square D breakers because of the increased reliability

required in this powering application. High-magnetic Square D circuit breakers and a BBX option (UL Listed

service entrance) are available from Alpha Technologies.

NOTE:

Description

Alpha Part Number

Square D Part Number

120V Installation - High-magnetic (20A)

470-017-10

QO120HM

BBX - External Service Disconnect

020-085-10

QO2 -4L70RB

BBX - External Service Disconnect

020-141-10

QO8-16L100RB

In most cases, the following configurations qualify for service entrance use when wiring a duplex receptacle

to a service disconnect. Other codes may also apply. Always contact your local utility to verify that the wiring

conforms to applicable codes.

ATTENTION:

XM2-300HP Connections

When bonding the box to a neutral plate is required, use the long green bonding screw provided (Alpha P/N

523-011-10, Square D P/N 40283-371-50).

NOTE:

Proper 120Vac 20A service requires the installation site be:

Equipped with a 120Vac duplex receptacle which provides power to the power supply and

peripheral equipment.
Have a NEMA 5-20R receptacle is protected by a single-pole, 20 Amp High Magnetic (HM) circuit

breaker inside the service entrance.
Checked NEC CODE to verify proper wire AWG (suggested wire gauge is 12AWG).

Equipped with a grounding clamp, on the enclosure, to facilitate dedicated grounding.

9