Table 4-3, Minor Alarms

4.0

Operation, continued
4.4 Alarm Indications, continued

Minor Alarms

Active Alarm

Probable Cause of Alarm

Corrective Action

INPUT FAILURE

Utility AC Input has failed

1. CHECK AC INPUT

2. RESTORE AC INPUT

3. CONNECT GENERATOR

INPUT CURRENT LIMIT

AC Input current exceeds threshold setting.

1. REDUCE OUTPUT LOAD

2. CHECK INPUT CURRENT LIMIT SETTING

BATT DELTA MHO’S LOW

Conductance delta minor alarm threshold has been

exceeded.

1. CHECK ALARM THRESHOLD

2. REPLACE BATTERY

BATT TEMP PROBE

Remote Temp Sensor (RTS) failed or is not connected.

1. CHECK CONNECTION

2. REPLACE SENSOR

BATTERY AGING ALARM

The battery is nearing the expected end of life.

1. VERIFY BATTERY DATE

2. CHECK DATE/TIME