1.1

Theory of Operation, continued

Fig. 1-2, Simplified Block Diagram

1.1.2 Standby Operation

When the incoming AC line voltage drops or rises significantly, or a complete power

outage occurs, the control logic’s line monitor activates standby operation. During the

transfer from AC line to standby operation, the battery powered inverter comes online

as the isolation relay switches to prevent AC power from back-feeding to the utility.

The following changes also occur within the XM2-300HP:

The isolation relay opens to disconnect the AC line from the primary winding of

the transformer.

The control logic drives the inverter FETs on and off at line frequency. This

switching action converts the DC battery current into AC current in the inverter

windings of the transformer, providing regulated power to the load.

The control logic, which includes a microprocessor and other circuits to protect

the inverter FETs from overcurrent damage, monitors the condition of the battery

and the inverter during standby operation. Since a prolonged AC line outage

would severely discharge the battery, resulting in permanent damage, the control

logic disables the inverter when the battery drops to approximately 10.5Vdc.

When acceptable AC line voltage returns, the power supply returns to AC line

operation after a 20 to 40 second lag. This delay lets the AC line voltage and

frequency stabilize before the control logic phase-locks the inverter’s output to the

utility input. The control logic then de-energizes the isolation relay, reconnects the AC

line to the primary of the transformer and disables (turns off) the inverter. This results

in a smooth, in-phase transfer back to utility power without interruption of service

to the load. The battery charging circuit then activates to recharge the battery in

preparation for the next power outage.

OUTPUT 1

OUTPUT 2

LRI

TRANSFORMER

INVERTER

BATTERY

INVERTER MODULE ASSEMBLY

POWER DISTRIBUTION BOARD

COAXIAL NETWORK

STATUS MONITORING

CONNECTION

OPTIONAL

COMMUNICATIONS

CARD AND

TRANSPONDER

OUTPUT

VOLTAGE TAP

SELECTOR

SERVICE

POWER INSERTER

(ALPHA SPI)

OPTIONAL SURGE PROTECTOR

REPLACEABLE PRIMARY POWER SUPPLY

OVERVOLTAGE PROTECTION

AC LINE DETECTION

AND CONTROL LOGIC

CIRCUITS

DUAL REMOTE

TEMPERATURE

SENSOR

SURGE PROTECTION

LRI CONTROL CIRCUIT

OUTPUT

CIRCUIT

BREAKER

14

017-877-B1-001 Rev. A

Advertising
This manual is related to the following products: