4.0

Operation, continued
4.3

Smart Display modes for XM2-300HP, continued

4.3.3 Setup Menu, continued

The Setup Menu contains the following items:

Top Line (provides additional information)

SET UP MENU

TO MANUAL SCROLL

<ESC> TO COMMS INFO

Second Line (cycles through the following parameters):

See Section 4.7 Smart Display Glossary for descriptions of setup menu parameters.

NOTE:

Default

Minimum

Maximum

Other Battery Types

Other

If AlphaCell™ is selected then user

selects between a range of Alpha cells

Device Address

1

0

7

Battery 1 Life

5

0

10

MHO’s Minor Level

80%

10

60

MHO’s Major Level

60%

20

100

Float V/C

2.27 V/C

2.10 V/C

2.35 V/C

Accept V/C

2.40 V/C

2.20 V/C

2.45 V/C

Temp Comp

5.0 mV

0.0 mV

5.0 mV

Batt. Capacity*

100 AH

0

1000 AH

Battery 1** Date

01/10

01/10

01/10

Battery 1 MHOS

1050 S

0 S

9999 S

MHO 1 Date

01/10

01/00

12/30

Battery 1 Life

5 Y

0 Y

10 Y

Battery 1 Age

0

0 (Read Only)

0 (Read Only)

MHO’s Minor Level

80%

20%

80%

MHO’s Major Level

60%

20%

80%

Standby Time

0

0

65335

Standby Events

0

0

65335

Total Runtime

0

0

65335

Self Test

Off

Off

Yes

Test Interval

30 Days

0 Days

360 Days

Test Inhibit

7 Days

7 Days

Discharge %

00%

00%

50%

Test Duration

10 Min

5 Min

180 Min

Test Countdown

30 Days

0 Days

360 Days

Freq. Range

3.0Hz

1.0Hz

6.0Hz

PIM Option

Yes

No (Read Only)

Yes (Read Only)

Reset Output 1

No

Yes

Reset Output 2

No

Yes

Over Curr1

5.0 A

3.0 A

6.0 A

Over Curr2

5.0 A

3.0 A

6.0 A

Retry Delay

300 Sec

60 Sec

600 Sec

Retry Limit

10

0

10

Over Curr Tol

60s

0s

255s

System Fan

No

No

Yes

PS Priority

High

Normal

Critical

Technician ID

123

000

999

Input I Limit

6.0 A

1.0 A

6.0 A

Set Defaults

No

Yes

Language

English

Spanish/French/Portuguese/German

These items

appear in the setup

menu only

if battery type

Other is selected.

They are preset

(but not displayed)

if AlphaCell™ is

selected.

These items

appear in the setup

menu only

if the optional

PIM is installed.

40

017-877-B1-001 Rev. A