Alpha Technologies XM2-300CE-HP User Manual
Page 41

Fig. 4-6, Setup Menu Display
(Examples are given for values in the display)
4.0
Operation, continued
4.3
Smart Display modes for XM2-300HP, continued
4.3.3 Setup Menu, continued
SETUP MENU
CODE VER
7.01.0
DEVICE ADDRESS
1
ALPHACELL
OTHER
FLOAT V/C
2.27
ACCEPT V/C
2.40
TEMP COMP
5mV
BATT CAPACITy
100Ah
# BATT STRINGS*
1
BATT 1 DATE M/y*
01/10
BATT 2 DATE M/y**
01/10
BATT 1 MHOS*
1050
BATT 2 MHOS**
1050
MHO 1 DATE M/y*
01/10
MHO 2 DATE M/y**
01/10
BATTERy 1 LIFE*
5y
BATTERy 1 AGE*
5y
BATTERy 2 LIFE**
0 MO
BATTERy 2 AGE**
0 MO
MHOS MIN LEVEL*
80%
MHOS MAJ LVL*
60%
STANDBy TIME
65 M
STANDBy EVENTS
12
TOTAL RUN TIME
365D
SELF TEST
OFF
TEST INTERVAL
30D
TEST INHIBIT
—
% DISCHARGE
00%
TEST DURATION
10 M
TEST COUNTDOWN
30D
FREq RANGE
3.0Hz
PIM OPTION
yES
RESET OUTPUT 1
—
RESET OUTPUT 2
—
OVER CURR 1
15.0A
OVER CURR 2
15.0A
RETRy DELAy
60S
RETRy LIMIT
20
OVER CURR TOL
3000ms
SySTEM FAN
NO
HEATER MAT
NO
PS PRIORITy
NORMAL
TECHNICIAN ID
123
INPUT LIMIT
6.0
SET DEFAULTS
NO
SELECT LANGUAGE
ENGLISH
* Visible in Single Step Mode
**Visible when “Number of Battery
Strings” is set to 2.