2 installing the optional ac indicator (aci) lamp – Alpha Technologies XM2-300CE-HP User Manual

Page 23

Advertising
background image

ACI Option

The AC indicator (green lamp) is located on the outside of the enclosure. When lit, it indicates

AC power is available at the power supply output and enables service personnel to determine

the status of the power supply without having to climb the pole.

Installation Procedure:

Remove the rear-most knockout (see Fig. 2-3).

1.

Feed ACI wires through the hole.

2.

Slide locking nut over the wires and thread onto lamp body

3.

(see Fig. 2-1).

Insert the crimped contacts into the plastic connectors. The BLACK wire must always go

4.

into the BLACK housing. Insert the remaining wire (this may be white, yellow, or blue) into

the WHITE housing (see Fig. 2-2).

Connect the shorter BLACK/WHITE set of wires to the BLACK/WHITE wires leading from

5.

the SPI. The remaining set of longer wires connects to the Output 1 connector on the

front of the XM2-300HP (Fig. 2-3).

Fig. 2-1, AC Indicator

Enclosure Wall

Fig. 2-2, Wire/Housing Assembly

Top View

White Housing

Black Housing

Black Wire

White, Yellow, or Blue Wire

Verify contact snaps

over metal retainer

Side View

2.0

Installation, continued

2.2 Installing the Optional AC Indicator (ACI) Lamp

Secure the contact. If you do not properly position the contact, overheating and cable assembly

failure can result.

CAUTION!

To remove the wire from the plastic connector, use a small screwdriver to depress the metal retainer and slide

out the wire.

NOTE:

To SPI

To Output