4.0

Operation, continued
4.4 Alarm Indications, continued

Table 4-2, Major Alarms

Note 1: To clear a Latched Self-Test Fail Alarm, initiate and complete a successful self-test.

Note 2: Remove and replace XM2-300HP.

Do not try to clear alarm or while in service.

NOTE:

Major Alarms

Active Alarm

Probable Cause of Alarm

Corrective Action

SELF TEST STATUS

Output voltage failed or batteries less than 1.85V/cell

during Selt Test.

1. CHECK BATTERIES

2. CHECK INVERTER

Refer to Notes below for additional information.

INVERTER STATUS

Predicted overall health of the inverter calculated by the

power supply’s proprietary algorithm.

1. CHECK INVERTER

2. REPLACE INVERTER

OUTPUT OVERLOAD

The output is overloaded or shorted.

1. REMOVE SHORT CIRCUIT

2. REDUCE OUTPUT LOAD

3. REPLACE POWR SPLY

OUTPUT 1 TRIPPED

Output 1 PIM hardware protection mode engaged and

is overloaded.

1. REDUCE OUTPUT LOAD

2. CHECK PIM SETTINGS

CHARGER FAILURE

Charger has failed or shutdown, possible battery over-

temperature.

1. RESEAT INVERTER

2. PERFORM SELF TEST

3. REPLACE INVERTER

INVERTER TEMP

Inverter heat sink has exceeded set temperature (Stand-

by operations suspended until temp drops to safe level).

1. CHECK VENTILATION

2. REPLACE INVERTER

CONFIG ERROR

The power supply is improperly configured and opera-

tion is suspended until error is corrected.

1. CHECK INVERTER MODULE

BATTERY STATUS

Predicted overall health of the batteries calculated by

the power supply’s proprietary algorithm.

1. CHECK BATTERIES

2. REPLACE BATTERIES

LOW BATT WARNING

Batteries dropped below 1.85 V/cell.

1. SHUTDOWN IMMINENT

2. CHECK AC INPUT

3. CONNECT GENERATOR

HIGH BATT WARNING

Batteries raised above 2.50 V/cell.

1. CHECK CHGR SETTINGS

2. REPLACE INVERTER

BATT DELTA MHO’S VERY

LOW

Conductance delta major alarm threshold has been

exceeded.

1. CHECK ALARM THRESH

2. REPLACE BATTERY

OUTPUT FAIL

Power Supply output has failed.

1. CHECK OUTPUT TYPE

2. OUTPUT OVERLOADED?

3. CHECK INVERTER

LINE ISOLATION

AC plug is connected to the inverter. The potential for

backfeed exists.

1. REPLACE POWER SUPPLY

45